TN-S

An system where the supply itself provides a separate earth conductor back to the source. Traditionally that conductor is the lead sheath or armour of the distributor's cable. Neutral and earth stay separate throughout, which keeps the earth path clean but depends entirely on the integrity of that supply conductor.

Where TN-S fits in the learning path

The Installation section covers these units:

  • Wiring Systems & Enclosures
  • Cable Selection & Circuit Design
  • Earthing, Bonding & Consumer Units

Curriculum mapping: C&G 2365 Units 203/204/305.

See this section in the full curriculum

This section is on the Plus path. Lesson availability depends on content review and your learning path.

Read, practise, return

  1. 1. Read it in context

  2. 2. Try recalling, then explore practice

    Use the memory prompt below to connect the vocabulary.

    Follow a topic above to explore how the term is used, then use the learning entry below to find your path.

  3. 3. Return to the meaning

    After reading or practising, explain the idea in your own words. Revisit the TN-S definition to check what you remembered.

Recall a related term

Which term fits this definition? Say it to yourself, then reveal it. This is a memory prompt, with no score or saved result.

The most common modern UK supply arrangement: the distributor combines neutral and earth in a single conductor (the PEN) up to the service head, where it splits into separate neutral and earth for the installation. Its weakness is a broken PEN conductor, which can put the whole installation's earthed metalwork at a dangerous voltage — the reason special rules apply to EV charging and other outdoor equipment on PME supplies.

Open a meaning to compare its role with TN-S, or follow its full entry.

TN-C-S — Protective Multiple Earthing (PME)

The most common modern UK supply arrangement: the distributor combines neutral and earth in a single conductor (the PEN) up to the service head, where it splits into separate neutral and earth for the installation. Its weakness is a broken PEN conductor, which can put the whole installation's earthed metalwork at a dangerous voltage — the reason special rules apply to EV charging and other outdoor equipment on PME supplies.

Read the TN-C-S entry
TT system

An earthing system where the installation provides its own earth via an electrode in the ground. Common on rural and overhead supplies, it takes no earth from the distributor at all. The soil path makes the earth fault loop impedance high, so an RCD, not the overcurrent device, is what disconnects earth faults on a TT installation.

Read the TT system entry
Earthing

Connecting an installation's exposed metalwork to earth and back to the supply source. That gives fault current a deliberate low-impedance path home, turning a live casing into a large, brief fault current that the protective device can detect and disconnect — without it, the casing simply stays live.

Read the Earthing entry
Ze — External Earth Fault Loop Impedance

The portion of the earth fault loop that lies outside the installation — the supply transformer winding, the distributor's cables and the earth return path, measured at the origin with the installation's own parallel paths disconnected. Ze depends on the earthing system: a TT installation relying on an electrode in soil sees a far higher value than a TN supply with a metallic return.

Read the Ze entry