Rated short-circuit capacity

Icn

The highest fault a circuit breaker can break under BS EN 60898-1, shown in the box on its front. The breaker may not be fit for further use after clearing a fault that size. Its has to suit the where it's installed, unless a device further up the supply backs it up.

Where to look it up: BS EN 60898-1; BS 7671 Regulation 434.5.1.

Using Rated short-circuit capacity in context

Reviewed

A distinction worth remembering

Load current is what equipment draws in normal use. Prospective fault current is the largest current a fault could drive at a given point, and it decides what the protective device there has to be able to break. A device's rated current and its breaking capacity are separate specifications, so a breaker that's right for the load can still be wrong for the fault.

Questions to take further

How can I revise Rated short-circuit capacity beyond the definition?
Explain what Rated short-circuit capacity describes, compare it with a related term and use it in a topic question. State any assumptions and what evidence you would need before applying the idea to real work.

Sources

Report a mistake

Where Rated short-circuit capacity fits in the learning path

The Design Calculations section covers these units:

  • Sizing a Cable, Every Factor
  • Volt Drop and Zs in Depth
  • Fault Current, the Adiabatic Check and Device Choice
  • Submains, Three-Phase Boards and Demand

Curriculum mapping: C&G 2365 Unit 305.

See this section in the full curriculum

This section is on the Plus path. Lesson availability depends on content review and your learning path.

Read, practise, return

  1. 1. Read it in context

  2. 2. Try recalling, then explore practice

    Use the memory prompt below to connect the vocabulary.

  3. 3. Return to the meaning

    After reading or practising, explain the idea in your own words, then check what you remembered.

    Revisit the Rated short-circuit capacity definition

Recall a related term

Which term fits this definition? Say it to yourself, then reveal it. This is a memory prompt, with no score or saved result.

The largest prospective fault current that a protective device can interrupt safely under its stated conditions. If the available fault current exceeds that rating, the device may fail while trying to clear a short circuit. Selection compares the device rating with the fault current possible at its point in the installation.

Open a meaning to compare its role with Rated short-circuit capacity, or follow its full entry.

Breaking capacity

The largest prospective fault current that a protective device can interrupt safely under its stated conditions. If the available fault current exceeds that rating, the device may fail while trying to clear a short circuit. Selection compares the device rating with the fault current possible at its point in the installation.

Read the Breaking capacity entry
Service short-circuit capacity — Ics

The largest fault current a circuit breaker can clear and still be fit to stay in service. Under BS EN 60898-1 it's linked to Icn: a 6 kA breaker also has an Ics of 6 kA, but a 10 kA breaker has an Ics of 7.5 kA. It matters where a circuit has to keep working after a big fault, because above Ics the breaker may need replacing.

Read the Service short-circuit capacity entry
PFC — Prospective Fault Current

The current that could flow at a point if a fault of negligible impedance occurred there. Assessment considers the relevant short-circuit and earth-fault conditions. Protective devices must have adequate breaking capacity, or a verified coordinated arrangement with upstream protection, for the fault current at their location.

Read the PFC entry
MCB — Miniature Circuit Breaker

An automatic switch that turns a circuit off when too much current flows, whether a slow overload or a sudden short circuit. It has replaced the rewirable fuse in modern boards. Each one is chosen by its current rating, such as 6 A for lights or 32 A for sockets, and by its type: B for most home circuits, C or D where equipment draws a big surge as it starts.

Read the MCB entry

A definition is a start. Using it in a real question is where it sticks.

By starting, you agree to our Terms and Privacy notice.